RM7840L1075

RM7840L1075 Honeywell Programmer Control On / Off with LF Proven Purge.

In Stock (40)

Availability: In stock

$4,368.94
Honeywell

HVAC Parts, Honeywell, York, Trane, AO Smith, Carrier, Armstrong, Lennox and Fasco

Honeywell Trane Carrier Customer Service

Hard To Find Parts for AO Smith, York, ASCO, and more

Details
Details

RM7840L1075 Overview

Honeywell RM7840L1075 Integrated burner control for gas, oil, coal or combination fuel single burner uses. Provides safety, functional capability and features beyond normal controls. With Valve Proving Feature. RM7840 requires S7800A1142 Keyboard Display.

Features

  • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting.
  • Access for external electrical voltage checks.
  • Application flexibility and communication interface capability.
  • Five LEDs provide sequence information. Power LED blinks fault code on Lockout.
  • Five function Run/Test Switch.
  • Interchangeable plug-in flame amplifiers.
  • Local or remote annunciation of operation and fault information (optional).
  • Nonvolatile memory retains history files and lockout status after loss of power.
  • Compatible with existing Honeywell flame detectors.
  • RM7840L1075 comes with S7800A1142 Keyboard Display Module.
  • Keyboard required to setup Valve Proving Feature and change post purge time.

Product Specifications

Application Programming Control w/VPS
Dimensions (in.) 5 in. wide x 5 in. high x 5 1/4 in. deep with
Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
Dimensions (mm) 127 mm wide x 127 mm high x 133 mm deep with
Q7800A Subbase x 155 mm deep with Q7800B Subbase
Weight (lb) 1 lb 10 oz
Weight (kg) 0.7 kg
RM7840L1075 Comments Requires S7800A1142 Display, LHL-LF&HF Proven
Frequency 50 Hz; 60 Hz (±10%)
Approvals, Underwriters Laboratories Inc. Component Recognized, File No. MP268; Guide No. MCCZ.
Voltage 120 Vac (+10, -15%)
Shipping and Storage Temperature Range (F) -40 F to +140 F
Shipping and Storage Temperature Range (C) -40 C to +60 C
Approvals, Federal Communications Commission FCC Part 15, Class B, Emissions.
Flame Establishing Period - Pilot 4 sec or 10 sec
Flame Establishing Period - Main 10 sec or 15 sec
Interlocks Lockout
Preignition Yes
PrePurge Determined by ST7800A Purge Timer Card
PostPurge programmed with S7800A1142 display
Early Spark Termination Yes, 5 sec
Required Components Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849,
R7851, R7852, R7861, or R7886 Flame Signal Amplifier.
ST7800A Plug-in Purge Timer Card.
AirFlow Check User selectable
Second Stage Pilot Valve selectable
Pilot Type interrupted
Vibration 0.5 G environment
RM7840L1075 Approvals, Factory Mutual Report No. 1V9AO.AF.
Additional Info
Additional Info
Name RM7840L1075
Documentation No
Manufacturer Honeywell
UPC: RM7840L1075
Reviews
Customer Reviews (1)
RM7840L1075 Great Service - Early AM
I just wanted to thank you very much for the service I received yesterday on this item, RM7840L1075.

I called late in the day, needing the part next day, early am delivery. I was assured by the two professional people I spoke with that I would get it on time, (but I really had doubts). However, just as promised UPS showed up at 7:30 and by 8:00 am the part RM7840L1075 was installed and we were back up and running.

Being in the service business, I know sometimes the customer has expectations, but doesn’t always leave you with many options, as I did in this case. But your company was able to exceed my expectations.

Again I just wanted to say thank you very much.
Review by Barry Cannon (Posted on 4/8/2015)
Write Your Own Review

Only registered users can write reviews. Please, log in or register

Post your comment

Parts-HVAC